| Attic floor area | 1,200 sq ft |
|---|---|
| Code ratio | 1/150 (2021 IRC R806.2 minimum) |
| Total net free area needed | 1,152 sq in, half exhaust and half intake |
| Exhaust (upper) | 576 sq in ÷ 18 sq in per ft = 32 ft of ridge vent (576 sq in installed) |
| Intake (lower) | at least 576 sq in ÷ 9 sq in per ft = 64 ft of continuous soffit vent (576 sq in installed, never less than the exhaust) |
Net free area differs between products, so check the label on the vents you buy and divide by its number. Use one type of exhaust vent per attic: Air Vent warns that mixing a ridge vent with gable vents, louvers or a fan short-circuits the airflow, and DOE says the same about gable vents.